Permit: T07CM02769

Parcel: 12706010A


Addresses:

40 N SWAN RD 02

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH #1 & #2 OF PREVIOUS INSPECTION
08/03/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VDV CABELING TO BE SUPPORTED AS PER 725.6 & 800.6
2. BOXES MORE THAN 1/8" -- 314.21
3. EM LIGHTING TO BE ON CIRCUIT SERVING AREA -- 700.12
4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR
5. MAINTAIN WORKING CLEARANCES AT
A/C DISCONNECT -- 110.26
6. NEED MAINTENANCE RECEPTACLE ON ROOF -- 210.16

OK TO TILE EXCEPT AS NOTED