Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02769
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/06/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH #1 & #2 OF PREVIOUS INSPECTION |
|
08/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VDV CABELING TO BE SUPPORTED AS PER 725.6 & 800.6 2. BOXES MORE THAN 1/8" -- 314.21 3. EM LIGHTING TO BE ON CIRCUIT SERVING AREA -- 700.12 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 5. MAINTAIN WORKING CLEARANCES AT A/C DISCONNECT -- 110.26 6. NEED MAINTENANCE RECEPTACLE ON ROOF -- 210.16 OK TO TILE EXCEPT AS NOTED |