Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/21/2007 | FRAMING | Denied | ||
| 09/07/2007 | FRAMING | Partial Approval | ||
| 09/06/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LEAK AT 1/2" PEX BY 6050 2) SHEARWALL AT STAIRS REQUIRES A35 CLIPS AT 8" ON CENTER |
|
| 09/05/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LEAK ON PEX MANIFOLD BY 6050 2) STAIR SHEAR REQUIRES A35 CLIPS AT 8" ON CENTER AT TOP PLATE AND 16D NAILS AT 6" ON CENTER |
|
| 08/31/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER HORACE |
|
| 08/30/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) STUCCO NOT COMPLETE 2) HOLDOWNS NOT INSTALLED 3) ? ROOM STACK CLEANOUT MISSING 4) DUCT BOOTS NOT BLOCKED 5) KITCHEN SHEARWALL NOT CONNECTED TO TRUSS SYSTEM. PROVIDE APPROVED DETAIL 6) SILL PLATES REQUIRE 2 ANCHOR BOLTS 7) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE SPLICES 8) KITCHEN VENT STACK MISSING 9) STOPPED INSPECTION-TOO MANY ITEMS |