Permit: T07CM02761

Parcel: 140552110

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/07/2007 FRAMING Approved IVRS - Inspection :*
09/21/2007 FRAMING Denied
09/07/2007 FRAMING Partial Approval
09/06/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LEAK AT 1/2" PEX BY 6050
2) SHEARWALL AT STAIRS REQUIRES A35 CLIPS AT 8" ON CENTER
09/05/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LEAK ON PEX MANIFOLD BY 6050
2) STAIR SHEAR REQUIRES A35 CLIPS AT 8" ON CENTER AT TOP PLATE AND 16D NAILS AT 6" ON CENTER
08/31/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER HORACE
08/30/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) STUCCO NOT COMPLETE
2) HOLDOWNS NOT INSTALLED
3) ? ROOM STACK CLEANOUT MISSING
4) DUCT BOOTS NOT BLOCKED
5) KITCHEN SHEARWALL NOT CONNECTED TO TRUSS SYSTEM. PROVIDE APPROVED DETAIL
6) SILL PLATES REQUIRE 2 ANCHOR BOLTS
7) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE SPLICES
8) KITCHEN VENT STACK MISSING
9) STOPPED INSPECTION-TOO MANY ITEMS