Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM02757
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE 2) OK FOR FINAL |
|
09/04/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
08/28/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AN ADULT MUST BE PRESENT AT TIME OF INSPECTION 2) I CANNOT GO INTO AN OCCUPIED HOME WITHOUT AN ESCOURT |
|
08/21/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE SWITCHES AT ALL FAN COILS 2) FINISH CONDENSATE DRAIN PIPING |
|
07/23/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROPER CONDUCTORS FOR 230V SUPPLY TO CONDENSORS, NO WHITE WIRE 2) PROVIDE 15 AMP DISCONNECTS AT EACH FAN COIL PER MANUFACTURERS INSTRUCTIONS 3) CONDENSATE CANNOT TERMINATE ONTO THE PATIO OR SIDE WALK 4) SECURE CONDENSORS TO PADS |