Permit: T07CM02757

Parcel: 136048320

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM02757

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
2) OK FOR FINAL
09/04/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
08/28/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AN ADULT MUST BE PRESENT AT TIME OF INSPECTION
2) I CANNOT GO INTO AN OCCUPIED HOME WITHOUT AN ESCOURT
08/21/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE SWITCHES AT ALL FAN COILS
2) FINISH CONDENSATE DRAIN PIPING
07/23/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROPER CONDUCTORS FOR 230V SUPPLY TO CONDENSORS, NO WHITE WIRE
2) PROVIDE 15 AMP DISCONNECTS AT EACH FAN COIL PER MANUFACTURERS INSTRUCTIONS
3) CONDENSATE CANNOT TERMINATE ONTO THE PATIO OR SIDE WALK
4) SECURE CONDENSORS TO PADS