Permit: T07CM02757

Parcel: 136048320

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T07CM02757

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
10/15/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LISTING FOR TOTO S-300 WASHLET
2) PROVIDE CERT FOR LANDSCAPING BACKFLOW DEVICE
3) RECEIVED STERILIZATION AND BACTERIA REPORT
10/14/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ALL OF LIST 8/21/09
10/13/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED
10/05/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS AT 10:35 TO INTERIOR ITEMS
2) SEE ITEMS CIRCLED AND MAKE CORRECTIONS
10/01/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY WALTER
08/28/2009 PLUMBING - FINAL Cancelled IVRS - RI canceled
08/21/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE STERILIZATION AND BACTERIA REPORT FOR WATER SYSTEM
2) EXPOSE EXTERIOR 2 WAY CLEANOUT
3) SECURE KITCHEN SINK FAUCET (IS DRINKING FOUNTAIN LISTED FOR EXTERIOR USE ?)
4) PROVIDE CLAMP FOR HIGH LOOP TO UNDER COUNTER OF KITCHEN SINK FOR DISHWASHER DRAIN HOSE
5) PROVIDE LISTING INFORMATION OR STOOL INSTALLATION INSTRUCTIONS
6) PROVIDE APPROVED BACKFLOW PROTECTION FOR LANDSCAPING WATER SUPPLY WITH VALVE DOWN STREAM OF VACUUM BREAKER
7) SECURE EXPANSION TANK PROPERLY
8) PROVIDE HAMMER ARRESTORS AT LAUNDRY BOX
9) PERMANENT CAP WATER AND DRAIN OPPOSITE P-10
07/23/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED