Permit: T07CM02757

Parcel: 136048320

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T07CM02757

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
11/28/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CHECK PLAN FOR GROUNDING ELECTRODE SYSTEM
2. NOT SAFE TO TURN ON POWER
NEED TO BE TRIMMED OUT OR SET UP TEMP SERVICE OUTSIDE BUILDING WITH GFI RECEPT.
3. USE GROUND CLAMP LISTED FOR USE ON REBAR &
ALSO NEEDS TO BE ACCESSIBLE
11/13/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. NOT READY FOR POWER
2. COULD NOT LOCATE PLANS
3. NEED TO POST BOND WHEN READY FOR POWER