Permit: T07CM02757

Parcel: 136048320

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02757

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/19/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CANNOT USE FLEXIBLE CORD AS PERMANENT WIRING METHOD. CANNOT BE CONCEALED BY WALLS OR CEILINGS.
SEE NEC 400.7 AND 400.8
REMOVE WIRING NOT BEING USED
02/17/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
02/13/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
02/12/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL PREVIOUS INSPECTION ITEMS
2) NEXT UN-NECCESARY INSPECTION WILL RESULT IN RE-INSPECTION FEE
02/03/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL FIRE PUTTY PAD OVER ENTIRE RECEPT. AND SWITCH BOXES IN 2-HOUR WALL WHERE LESS THAN 24" SEPARATION PER INSTRUCTIONS
2. INSTALL LISTED FAN BOX OFFICE #2
3. PLANS SHOW NO RANGE CIRCUIT/PLAN CALLS FOR 6-2 TO CLOTHES DRYER INSTALL CONNECTION ON 8/3 @ BOX
4. STILL MISSING RECEPT UNDER 3-GANG SWITCH LIVING RM.
5. FIRE RESISTIVE INFO. PROVIDE IS FOR CARLON BOXES NOT PASS AND SEYMAR BOXES
6. PROVIDE INFO. ON OPEN SPLICES FOR SPLIT AC UNITS
01/05/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANCAKE BOX CEILING IN OFFICES ARE NOT SHOWN ON PLANS. IF FOR CEILING FAN NEEDS TO BE LISTED FOR CEILING FAN.
2. PROPERLY GROUND METAL BOXES
3. HANDY BOX FOR OUTDOOR RECEPT. NOT SIZED PROPERLY NEC 314.16
4. HAVE DAMAGED OUTER COVERING ON ROMEX
5. WHERE ARE EXHAUST FANS IN OFFICES TO ABE INTERLOCKED WITH AC UNITS. MISSING EXHAUST FAN LIVING ROOM
6. HAVE OPEN SPLICES FOR SPLIT AC UNITS
IS THIS LOW VOLTAGE?
7. MISSING RECEPT FOR REQUIRED WALL SPACE
8. EXPLAIN 20 AMP. CIRCUIT FOR RANGE
9. PLEASE EXPLAIN ADA RESTROOM
10. VERIFY PLASTIC BOXES RATED FOR FIRE WALLS AND NEED PROPER BOX SPACING
11. ROMEX NOT TO BE STAPLED ON EDGE
12. HAVE HANGING WIRES