Permit: T07CM02757

Parcel: 136048320

Inspection Status: Approved

Inspection History: FIREWALL/FIREBARRIER/FIRESTOP

Permit Number - T07CM02757

Inspection Description - FIREWALL/FIREBARRIER/FIRESTOP

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2009 FIREWALL/FIREBARRIER/FIRESTOP Approved IVRS - Inspection :*
12/10/2008 FIREWALL/FIREBARRIER/FIRESTOP Denied IVRS - Inspection :
See detailed listing on site.| 999*
W2 - 1HR. FIRE WALL @ SOUTH/WEST EXTERIOR CORNER HAS NO 5/8" DRYWALL ON OUTSIDE AS PER W-2 DETAIL ON SHEET A4.0 AND RELOCATED DOOR #05 MUST BE REFLECTED ON DRAWINGS BY ARCHITECT