Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T07CM02735
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) PROVIDE TORQUE LETTER 2) BOND GAS PIPING |
|
12/17/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* WIRING NOT PER PLAN. NEED TO REVISE SINGLE LINE DIAGRAM TO SHOW ACTUAL SCOPE OF WORK. ALSO, PLAN REVISION FOR SINGLE LINE DIAGRAM TO ALSO REFLECT AVAILABLE FAULT CURRENTS, REVISED PLANS MUST BE RE-SUBMITTED THROUGH PLAN REVIEW WITH THE CITY OF TUCSON (ORIGINAL PLAN REVIEWER) NO INSPECTION AT THIS TIME |