Permit: T07CM02735

Parcel: 123110110


Addresses:

1540 E LINDEN ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T07CM02735

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/18/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) PROVIDE TORQUE LETTER
2) BOND GAS PIPING
12/17/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
WIRING NOT PER PLAN. NEED TO REVISE SINGLE LINE DIAGRAM TO SHOW ACTUAL SCOPE OF WORK. ALSO, PLAN REVISION FOR SINGLE LINE DIAGRAM TO ALSO REFLECT AVAILABLE FAULT CURRENTS, REVISED PLANS MUST BE RE-SUBMITTED THROUGH PLAN REVIEW WITH THE CITY OF TUCSON (ORIGINAL PLAN REVIEWER)

NO INSPECTION AT THIS TIME