Permit: T07CM02732

Parcel: 105102430

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02732

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/05/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
REVISED PLANS TO BE ON SITE
04/16/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PARTIAL FINAL APPROVED PENDING ACCEPTABLE REVISION OF PLANS TO REFLECT ACTUAL SCOPE OF WORK
OK TO OCCUPY AREAS
04/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FILL UNUSED OPENING - CONDUITS & BOXES
2. SUPPORT EMT AS PER CODES
3. SUPPORT VDV CABLING AS PER 725.4, 800.24, 300.11
4. EXPOSED CONDUCTORS ABOVE CEILING
5. SUPPORT MC CABLES AS PER 330.30 & 300.11
6. INSTALL ALL SCREWS FOR RECEPTACLES ON INDUSTRIAL COVERS
7. CORRECTLY IDENTIFY IG GROUNDS WITH YELLOW MARKINGS
8. USE TERMINAL ENDS TO TERMINATE STRANDED CONDUCTORS TO SCREWS
9. VERIFY ISOLATED GROUND SYSTEM WITH ENGINEER

* LOOK AT SERVICE NEXT INSPECTION
* REVISE PLANS FOR LIGHTING

RECEIVED MONEY ORDER #08-855367112 FOR $150.00
04/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMT TO BE SUPPORTED AT MAX. 10' INTERVALS

INSPECTION CANCELLED

ELECTRICIAN TO GO THROUGH COMPLETE JOB AND MAKE SURE IT IS PER PLAN AND PER CODE BEFORE CALLING FOR FINAL AREA IS OCCUPIED BEFORE APPROVAL. AFTER HRS. INSP. MAY BE NEEDED.