Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02732
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/05/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* REVISED PLANS TO BE ON SITE |
|
04/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PARTIAL FINAL APPROVED PENDING ACCEPTABLE REVISION OF PLANS TO REFLECT ACTUAL SCOPE OF WORK OK TO OCCUPY AREAS |
|
04/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FILL UNUSED OPENING - CONDUITS & BOXES 2. SUPPORT EMT AS PER CODES 3. SUPPORT VDV CABLING AS PER 725.4, 800.24, 300.11 4. EXPOSED CONDUCTORS ABOVE CEILING 5. SUPPORT MC CABLES AS PER 330.30 & 300.11 6. INSTALL ALL SCREWS FOR RECEPTACLES ON INDUSTRIAL COVERS 7. CORRECTLY IDENTIFY IG GROUNDS WITH YELLOW MARKINGS 8. USE TERMINAL ENDS TO TERMINATE STRANDED CONDUCTORS TO SCREWS 9. VERIFY ISOLATED GROUND SYSTEM WITH ENGINEER * LOOK AT SERVICE NEXT INSPECTION * REVISE PLANS FOR LIGHTING RECEIVED MONEY ORDER #08-855367112 FOR $150.00 |
|
04/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMT TO BE SUPPORTED AT MAX. 10' INTERVALS INSPECTION CANCELLED ELECTRICIAN TO GO THROUGH COMPLETE JOB AND MAKE SURE IT IS PER PLAN AND PER CODE BEFORE CALLING FOR FINAL AREA IS OCCUPIED BEFORE APPROVAL. AFTER HRS. INSP. MAY BE NEEDED. |