Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02732
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN IMPRESS HALF WALL |
|
02/27/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROPER SIZE WIRE NUTS 2. PREVIOUS CORRECTIONS |
|
02/25/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR CHECK OUT HALF WALL 1. WIRING NOT PER PLAN 2. BOXES TO BE BRACKET TYPE 4SQ OR USE BACK BRACKET NOT MOUNTED WITH SCREWS THROUGH SIDE - NEC 314.23 B1 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS - NEC 330.30 4. PROVIDE NAIL PLATES FOR FLEX & MC WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE - NEC 330.17 5. GROUND BOXES - NEC 250.148 |