Permit: T07CM02732

Parcel: 105102430

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/05/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN IMPRESS HALF WALL
02/27/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROPER SIZE WIRE NUTS
2. PREVIOUS CORRECTIONS
02/25/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR CHECK OUT HALF WALL
1. WIRING NOT PER PLAN
2. BOXES TO BE BRACKET TYPE 4SQ OR USE BACK BRACKET NOT MOUNTED WITH SCREWS THROUGH SIDE - NEC 314.23 B1
3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS -
NEC 330.30
4. PROVIDE NAIL PLATES FOR FLEX & MC WHERE HOLE IS LESS THAN 1 1/4" FROM STUD FACE - NEC 330.17
5. GROUND BOXES - NEC 250.148