Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SIZE EQUIP. SYSTEM GROUNDING AT X-FORMER PER 250.30 NEC (250.66) 2. INSTALL R-PINS IN SERVICE DISCONNECT 3. PLAN CALLS FOR 14K ARC ON PANEL "H" |
|
| 09/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BATHROOM WALLS AND HARD LID |