Permit: T07CM02711
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* SUPT. RON @ 269-9783 CONTR. REQUEST AFTER HRS. INSP. PAID CK#1094 - $150.00 |
|
| 07/28/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT VDV CABLING AS PER 725.3 & 800.3 & 725.24 & 800.24 & 300.11 2. MANUFACTURES FIXTURE CUPS TO BE EFFECTIVE - 410.16 3. EMT & BOXES TO BE SUPPORTED BOTH ENDS - 300.11, 358.30 ALSO 3' & 10" 4. M/C CABLE TO BE SUPPORTED AS PER 300.11 & 334.30 5. SUPPORT WIRES NEEDED FOR ALL FIXTURES |
|
| 07/07/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |