Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02709
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2007 | FRAMING | Approved | IVRS - Inspection :* | |
08/14/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEARWALL IN GARAGE NOT CONNECTED TO TRUSSES PER 5/D3 2) RED HEAD ANCHOR BOLTS LOOSE 3) TRUSS KNEE BRACES MISSING A-35 CLIPS PER 2/D2 4) A010 TRUSS MISSING RAT RUN TRUSS BRACE |