Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02703
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STRAP EMT WITHIN 3' OF PANELS & BOXES 2. NUMBER BREAKERS IN PANEL 3. STRAP MC & FLEX WITHIN 12" OF BOXES 4. INSTALL ALL MOUNTING SCREWS FOR RECEPTACLES ON INDUSTRIAL COVERS 5. SEAL OPEN KNOCKOUTS IN BOXES 6. CP PANEL NEEDS PANEL DIRECTORY 7. EMT COUPLING MISSING SCREWS 8. PROPERLY STRAP EMT 9. PLUG MOLD MISSING COUPLINGS, MISSING END CAPS, NOT PROPERLY CLOSED 10. PLUG MOLD WITH NO POWER 11. LABEL P-4 PANEL |