Permit: T07CM02703

Parcel: 137055240


Addresses:

1163 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02703

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STRAP EMT WITHIN 3' OF PANELS & BOXES
2. NUMBER BREAKERS IN PANEL
3. STRAP MC & FLEX WITHIN 12" OF BOXES
4. INSTALL ALL MOUNTING SCREWS FOR RECEPTACLES ON INDUSTRIAL COVERS
5. SEAL OPEN KNOCKOUTS IN BOXES
6. CP PANEL NEEDS PANEL DIRECTORY
7. EMT COUPLING MISSING SCREWS
8. PROPERLY STRAP EMT
9. PLUG MOLD MISSING COUPLINGS, MISSING END CAPS, NOT PROPERLY CLOSED
10. PLUG MOLD WITH NO POWER
11. LABEL P-4 PANEL