Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02700
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION 2. VERIFY 1 1/4" EMT HAS PROPER # OF WIRES 3. INSTALL PROPER BREAKERS IN CC PANEL 4. HAVE LIFT & JUNCTION BOXES IN CEILING OPEN NEXT INSPECTION 5. WHERE IS PANEL P-4? IF DELETED FROM PROJECT NEED TO REVISE PLANS 6. CHECK ALL 12" X 12" JUNCTION BOXES PROPERLY SECURED |
|
03/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES 2. INSTALL ALL MOUNTING SCREWS FOR RECEPT IN INDUSTRIAL COVERS 3. PLAN CALLS FOR 20 AMP RECEPTACLES & 20 AMP SINGLE RECEPT. 4. STRAP FLEX WITHIN 12" OF BOXES 5. NEED PANEL DIRECTORIES 6. CANNOT RUN EXTENSION CORD ACROSS FLOOR ADD ADDITIONAL RECEPTACLE IF NEEDED 7. PROPERLY STRAP MC CABLE CENTER DISPLAY 8. BOXES TO BE SECURED. CENTER DISPLAY. WHY ARE THERE SO MANY EXTENSIONS? IS THERE ENOUGH WIRE LENGTH? 9. SECURE BOXES AT REGISTERS. STRAP MC CABLE WITHIN 12" AT BOXES 10. HAVE INSTALLATION INSTRUCTIONS FOR POWER POLES & PLUG MOLD USE PROPER STRAP FOR SECURING POWER POLES AT CEILING 11. EMT TO BE STRAPPED WITHIN 3' OF BOXES 12. HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB HAVE CONTRACTOR ON SITE @ NEXT INSPECTION |