Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM02699
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/28/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/20/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DO NOT TERMINATE COOLER DRAIN TO A SEWER VENT 2) PROVIDE AIR BALANCE REPORT |
|
09/17/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONNECT THE HINGE ON EXHAUST FAN - SEAL TIGHT DOES NOT ALLOW FAN TO BE REMOVED PROPERLY - CONNECT THE GREASE DRAIN ON EXHAUST FAN - EXTEND SEWER VENT MIN. 2' ABOVE EVAP. COOLER - USE PROPER WIRING METHODS CONNECTING EVAP COOLER - DO NOT CUT THE PLUG OFF OF THE PUMP OR MOTOR - EVAP COOLER STAND NOT PER PLAN - PROVIDE A DRAIN FOR EVAP COOLER - PROVIDE AIR BALANCE REPORT - SEE BLDG. INSPECTOR FOR TEMP C OF O |