Permit: T07CM02699

Parcel: 12405142A


Addresses:

501 N PARK AV #120

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/28/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/20/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DO NOT TERMINATE COOLER DRAIN TO A SEWER VENT
2) PROVIDE AIR BALANCE REPORT
09/17/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONNECT THE HINGE ON EXHAUST FAN
- SEAL TIGHT DOES NOT ALLOW FAN TO BE REMOVED PROPERLY
- CONNECT THE GREASE DRAIN ON EXHAUST FAN
- EXTEND SEWER VENT MIN. 2' ABOVE EVAP. COOLER
- USE PROPER WIRING METHODS CONNECTING EVAP COOLER
- DO NOT CUT THE PLUG OFF OF THE PUMP OR MOTOR
- EVAP COOLER STAND NOT PER PLAN
- PROVIDE A DRAIN FOR EVAP COOLER
- PROVIDE AIR BALANCE REPORT
- SEE BLDG. INSPECTOR FOR TEMP C OF O