Permit: T07CM02699

Parcel: 12405142A


Addresses:

501 N PARK AV #120


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02699

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/12/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
ELECTRICIAN TO BE ON SITE
TO GO OVER THIS INSTALLATION
09/10/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
09/07/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OVERFILLED J-BOX USE A LARGER ONE NOT 4 SQ.
2. STRAP ALL MC FLEX WITHIN 12" OF TERMINATIONS, DON'T STRAP TO OTHER EQUIP.
3. ALL EQUIPMENT TO BE SECURED - USE ANCHORS WHERE NEEDED
4. CONTACTOR BOX TO BE METAL OR HAVE NON-METALLIC RACEWAY TO IT
5. WIRING/INTERLOCK TO BE PER PLAN -- FINISH ALL PREVIOUS CORRECTIONS.
09/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PREVIOUS CORRECTIONS NOT COMPLETED
2. WIRING IN CEILING NOT COMPLETED
3. WHERE IS GAS PIPE BONDED
4. DO NOT CALL BEFORE WORK COMPLETED
08/28/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL OPEN KNOCK OUT IN JUNCTION BOX
2. INSTALL BLANK COVER ON JUNCTION BOX
3. STRAP FLEX WITHIN 12" OF JUNCTION BOX
4. STRAP MC CABLE WITHIN 12" OF JUNCTION BOX
5. GROUND JUNCTION BOXES
6. WHERE IS CONTACTOR FOR HOOD INTERLOCK