Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02699
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/12/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ELECTRICIAN TO BE ON SITE TO GO OVER THIS INSTALLATION |
|
09/10/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
09/07/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OVERFILLED J-BOX USE A LARGER ONE NOT 4 SQ. 2. STRAP ALL MC FLEX WITHIN 12" OF TERMINATIONS, DON'T STRAP TO OTHER EQUIP. 3. ALL EQUIPMENT TO BE SECURED - USE ANCHORS WHERE NEEDED 4. CONTACTOR BOX TO BE METAL OR HAVE NON-METALLIC RACEWAY TO IT 5. WIRING/INTERLOCK TO BE PER PLAN -- FINISH ALL PREVIOUS CORRECTIONS. |
|
09/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PREVIOUS CORRECTIONS NOT COMPLETED 2. WIRING IN CEILING NOT COMPLETED 3. WHERE IS GAS PIPE BONDED 4. DO NOT CALL BEFORE WORK COMPLETED |
|
08/28/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCK OUT IN JUNCTION BOX 2. INSTALL BLANK COVER ON JUNCTION BOX 3. STRAP FLEX WITHIN 12" OF JUNCTION BOX 4. STRAP MC CABLE WITHIN 12" OF JUNCTION BOX 5. GROUND JUNCTION BOXES 6. WHERE IS CONTACTOR FOR HOOD INTERLOCK |