Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXIT LIGHT AT ENTRY TO HAVE EM LIGHTING ALSO 2. EM LIGHTS TO TIE INTO LIGHTING CIRCUIT IN AREA SECURED 3. NEED DETAILED PANEL SCHEDULE/NO ABBREVIATION NEC 408.4 |
|
| 09/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ELECTRICIAN TO GO THROUGH JOB AND INSTALL WATER HEATER BEFORE FINAL |