Permit: T07CM02696

Parcel: 122154490

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
09/12/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/11/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FINISH ALL LOW VOLTAGE WIRING, REMOVE COMPLETELY ALL UNUSED WIRING
2. HAVE OVERFILLED WIRE NUTS
3. HAVE OVERFILLED J-BOXES. IF CORRECT BOX VOLUME CAN'T BE ACHIEVED WITH ONE EXTENSION BOX, USE AT BIGGER J-BOX - DO NOT USE MORE THAN ONE EXTENSION
4. INSTALL REAR RECESSED CAN
5. HAVE SHORT IN CEILING CKT
6. LOW VOLTAGE WIRING NOT TO BE TIED TO OR SUPPORTED BY GRID OR OTHER EQUIPMENT -- INDIVIDUALLY SUPPORT.