Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM02688
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
07/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TRAP ARM MAY NOT CHANGE SIZE 2. TRAP AND TRAP ARM TO BE THE SAME SIZE 3. TRAP MAY BE ONLY ONE SIZE LARGER THAN TAILPIECE LAV TAILPIECE IS 1 1/4" 4. A DRAIN MAY NOT CONNECT TO A VENT |