Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/14/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) AIR BALANCE REPORT OK
2) ITEM 4 DATED 7/9/09 IS SUPERCEEDED BY LOCK, HOLD, NOTICE ABOVE DATED 7/10/09
3) DUCT SMOKE DETECTOR TEST OK
4) ALL OTHER ITEMS DATED 7/9/09 AND 6/17/09 COMPLETED
07/09/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) DUCT SMOKE DETECTORS TO BE TIED TO ALARM SYSTEM
2) PROVIDE INDEPENDENT BALANCE REPORT
3) COMPLETE ALL ITEMS DATED 7/17/09
4) PROVIDE WRITTEN APPEAL ON ITEM 4 DATED 6/17/09
06/29/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) AIR BALANCE REPORT NOT READY
06/18/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CUSTOMER CANCELLED
06/17/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL SIGHT GLASS AT C.U's
2. PAINT INSULATION AT C.U's
3. PROVIDE AIR BALANCE REPORT - MECHANICAL CONTRACTOR TO BE ON SITE FOR DUCT DETECTOR TEST
4. PROVIDE ACCESS FOR EQUIPMENT REMOVAL
04/27/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
04/24/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL EQUIPMENT PER DETAILS ON PLANS - VIBRATION ISOLATORS, SUCTION LINE RISERS, SIGHT GLASS.
2. BLUE SEAMS ON INSULATION
3. RELOCATE LINE SET BLOCKING BLOWER REMOVAL
4. NEED AIR BALANCE REPORT
5. NEED TO TEST DUCT SMOKE DETECTORS
6. PROVIDE TRAP PRIMER
03/05/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/27/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/26/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*