Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) AIR BALANCE REPORT OK 2) ITEM 4 DATED 7/9/09 IS SUPERCEEDED BY LOCK, HOLD, NOTICE ABOVE DATED 7/10/09 3) DUCT SMOKE DETECTOR TEST OK 4) ALL OTHER ITEMS DATED 7/9/09 AND 6/17/09 COMPLETED |
|
| 07/09/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS TO BE TIED TO ALARM SYSTEM 2) PROVIDE INDEPENDENT BALANCE REPORT 3) COMPLETE ALL ITEMS DATED 7/17/09 4) PROVIDE WRITTEN APPEAL ON ITEM 4 DATED 6/17/09 |
|
| 06/29/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) AIR BALANCE REPORT NOT READY |
|
| 06/18/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CUSTOMER CANCELLED |
|
| 06/17/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL SIGHT GLASS AT C.U's 2. PAINT INSULATION AT C.U's 3. PROVIDE AIR BALANCE REPORT - MECHANICAL CONTRACTOR TO BE ON SITE FOR DUCT DETECTOR TEST 4. PROVIDE ACCESS FOR EQUIPMENT REMOVAL |
|
| 04/27/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/24/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL EQUIPMENT PER DETAILS ON PLANS - VIBRATION ISOLATORS, SUCTION LINE RISERS, SIGHT GLASS. 2. BLUE SEAMS ON INSULATION 3. RELOCATE LINE SET BLOCKING BLOWER REMOVAL 4. NEED AIR BALANCE REPORT 5. NEED TO TEST DUCT SMOKE DETECTORS 6. PROVIDE TRAP PRIMER |
|
| 03/05/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/27/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/26/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |