Permit: T07CM02684

Parcel: 12215312A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/14/2009 MECHANICAL - INTERMEDIATE Approved
03/05/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/27/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OUTSIDE AIR OK
02/26/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK TO COVER RETURN AIR
2. PROVIDE ALL REQUIRED CLEARANCES AT MECHANICAL ROOMS
02/11/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE TRAP PRIMERS FOR CONDENSATE TO WASTE
2) WORK FROM LIST DATED 1/16/09 NOT DONE. ALL ITEMS MUST BE COMPLETE PRIOR TO NEXT INSPECTION TO AVOID REFEE
02/10/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ACCESS GATES LOCKED
01/16/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TERMINATE INSULATION SO AS NOT TO ALLOW FIBERS TO BLOW IN AIRSTREAM
2. REMOVE ALL COMBUSTIBLE MATERIALS FROM RETURN PLENUM
3. REPAIR ALL TORN INSULATION ON LINE SETS
4. NO GALVANIZED STRAPS TO TOUCH COPPER PIPE
5. SEAL ALL DUCT