Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2009 | ELECTRIC - INTERMEDIATE | Approved | ||
| 01/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LIDS FOR MECHANICAL CLOSETS BASED ON REVISION THAT ALLOWS USE OF MC CABLE. REVISION STILL NEEDS TO BE APPROVED BY PLANS EXAMINER. |
|
| 01/22/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE #3 ON SHEET E1 REQUIRES THE USE OF RACEWAYS AND DOES NOT ALLOW THE USE OF MC CABLE. RECALL WHEN READY. |
|
| 01/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT MC CABLES WITHIN 12" OF BOXES & PANEL 330.30 2. PROTECT MC CABLES AT STUDS - 330.4, 330.17 3. BROKEN MC SHEATHING |
|