Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM02682
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/13/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE REVISION REFLECTING REMOVAL OF SERVICE DRIVE ISLAND. ALL ELSE OK. |
|
10/08/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/31/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* #3, D.S.D TEST OK #4, D.S.D TEST OK # , D.S.D TEST OK PHASE 2 BALANCE AND DUCT SMOKE DETECTOR TEST OK SEE BLDG. INSPECTOR FOR TEMP C OF O PHASE II AREA ONLY |
|
07/29/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/30/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* AIR BALANCE OK TESTED DUCT SMOKE DETECTORS OK FOR FINAL PHASE I |
|
04/24/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - 1/2" ID X 18" GAS FLEX NOT ADEQUATE FOR 275,000 BTU - CONDENSATE CANNOT TERMINATE INTO A SEWER VENT - PROVIDE AUDIBLE & VISIBLE ALARMS ON DUCT SMOKE DETECTORS - PROVIDE AIR BALANCE REPORT |