Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM02682
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/08/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
07/21/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES PHASE 1 GRID LINES A TO D OK CEILING COVER EXTERIOR SOFFIT (CAR DISPLAY) PARTIAL |