Permit: T07CM02680

Parcel: 10409001C


Addresses:

4365 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM02680

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/10/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
VERTICAL 1 1/2" VENT REQUIRES SUPPORT
10/09/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS
NEED TO SEE OVERHEAD
REDLINE CHANGES TO THE PLAN
10/08/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. YOU SEEM TO BE MISSING PART OF YOUR PLAN
WHERE IS YOUR SCHEDULE OF MATERIAL TYPES TO BE USED
HANGERS REQUIRED ETC. INSULATION
2. IS-5 2006 UPC NO FEMALE ABS THREADED FITTINGS IN UNACCESSIBLE LOCATION
3. 1 1/2" VENT MAY ONLY RUN 20' HORIZONTAL
4. REVENT TO OCCUR AT LEAST 6" ABOVE FLOOD RIM OF CONNECTIVE FIXTURE
5. PLUMBERS TAPE NOT APPROVED STRAP
6. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS
7. ABS AND PVC MAY NOT BE INTERMINGLED
10/08/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*