Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM02680
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/10/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* VERTICAL 1 1/2" VENT REQUIRES SUPPORT |
|
10/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS NEED TO SEE OVERHEAD REDLINE CHANGES TO THE PLAN |
|
10/08/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. YOU SEEM TO BE MISSING PART OF YOUR PLAN WHERE IS YOUR SCHEDULE OF MATERIAL TYPES TO BE USED HANGERS REQUIRED ETC. INSULATION 2. IS-5 2006 UPC NO FEMALE ABS THREADED FITTINGS IN UNACCESSIBLE LOCATION 3. 1 1/2" VENT MAY ONLY RUN 20' HORIZONTAL 4. REVENT TO OCCUR AT LEAST 6" ABOVE FLOOD RIM OF CONNECTIVE FIXTURE 5. PLUMBERS TAPE NOT APPROVED STRAP 6. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS 7. ABS AND PVC MAY NOT BE INTERMINGLED |
|
10/08/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |