Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02679
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* RECALL AFTER CHEESE DISPLAY INSTALLED |
|
01/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ALL SUPPORT SCREWS ON RECEPTACLE IN INDUSTRIAL COVERS 2. SUPPORT EMT @ CASH REGISTERS WITHIN 3' OF BOXES 3. GROUND ALL METAL BOXES. CANNOT USE METAL FLEX AS GROUND PATH 4. INSTALL MISSING K.O SEAL JUNCTION BOX LOADING DOCK 5. CONNECT EQUIPMENT GROUND TO ROOFTOP DISCONNECTS 6. CONDENSING UNIT OVERFUSED 7. WATER HEATER OVERFUSED 8. WIRES SHORT TO ROOFTOP DISCONNECT 9. OK EM LIGHTS |