Permit: T07CM02679

Parcel: 128010190

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02679

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/31/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/30/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECALL AFTER CHEESE DISPLAY INSTALLED
01/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL ALL SUPPORT SCREWS ON RECEPTACLE IN INDUSTRIAL COVERS
2. SUPPORT EMT @ CASH REGISTERS WITHIN 3' OF BOXES
3. GROUND ALL METAL BOXES. CANNOT USE METAL FLEX AS GROUND PATH
4. INSTALL MISSING K.O SEAL JUNCTION BOX LOADING DOCK
5. CONNECT EQUIPMENT GROUND TO ROOFTOP DISCONNECTS
6. CONDENSING UNIT OVERFUSED
7. WATER HEATER OVERFUSED
8. WIRES SHORT TO ROOFTOP DISCONNECT
9. OK EM LIGHTS