Permit: T07CM02667

Parcel: 140420200

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02667

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK U.G SECONDARYS FROM EXISTING OUTSIDE SPLICE TO NEW SERVICE AREA TERM CAN - OK RESTROOM HARD LIDS
09/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- UTILITY CONDUCTORS NOT TO BE RUN THRU BLD. UNLESS MAIN DISCONNECT INSTALLED PER 250.70 NEC
- TERMINATIONS IN GUTTER MUST COMPLY WITH 366.56
09/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SERVICE CONDUCTORS NOT ALLOWED TO BE INSTALLED THRU BUILDING UNLESS AT TERMINATION INTO SERVICE EQUIP. AFTER IMMEDIATE ENTRANCE INTO BLD. 230.70 NEC
09/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLEASE REVISE PLANS TO INDICATE WHAT IS TO BE INSTALLED - INCLUDE WIRE SIZED AND CONDUCTOR MATERIALS
08/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS OFFICE, MEETING ROOMS