Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02667
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/08/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK U.G SECONDARYS FROM EXISTING OUTSIDE SPLICE TO NEW SERVICE AREA TERM CAN - OK RESTROOM HARD LIDS |
|
09/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - UTILITY CONDUCTORS NOT TO BE RUN THRU BLD. UNLESS MAIN DISCONNECT INSTALLED PER 250.70 NEC - TERMINATIONS IN GUTTER MUST COMPLY WITH 366.56 |
|
09/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SERVICE CONDUCTORS NOT ALLOWED TO BE INSTALLED THRU BUILDING UNLESS AT TERMINATION INTO SERVICE EQUIP. AFTER IMMEDIATE ENTRANCE INTO BLD. 230.70 NEC |
|
09/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PLEASE REVISE PLANS TO INDICATE WHAT IS TO BE INSTALLED - INCLUDE WIRE SIZED AND CONDUCTOR MATERIALS |
|
08/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS OFFICE, MEETING ROOMS |