Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/24/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) IN WALLS, ABOVE CEILING AND ROUGH SOIL OK, IN CLASS ROOMS #1 & #2 |
|
| 12/14/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHANGE THE ADDRESS ON THIS PERMIT TO THE CORRECT ADDRESS POSTED ON BUILDING TO OBTAIN FUTURE INSPECTIONS. WATER TEST RESTROOM & P-3 DWV OK WATER PIPING OK |
|
| 12/12/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL PROVIDE TEST ON DRAINAGE & VENT PIPING THAT IS NEW 2. PROVIDE CORRECT TRANSITION COUPLING FOR C.I TO PLASTIC |
|
| 10/16/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* KITCHEN & WASHER BOX AREA DWV THRU ROOF OK WATER PIPING SAME AREA OK PROVIDE BACKING FOR MOP SINK PRIOR TO DRYWALL |
|
| 10/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST INTERIOR DWV FOR 3-COMP SINK P4, P5 AND P8 IN KITCHEN AREA THRU ROOF OK WATER PIPING THIS AREA IS OK 1. SAME TEST THRU ROOF FOR LAUNDRY AREA AND COMPLETE WATER PIPING 2. SHALL PROVIDE FULL SIZE GREASE TRAP VENT THRU ROOF OK TIED INTO EXISTING VENT SYSTEM. |