Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RECALL WHEN READY |
|
| 01/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RECALL WHEN ALL HOOD WIRING IS COMPLETE 2. RECEPTACLE BACK OF RANGE TO BE TIED INTO ANSUL SYSTEM OR REMOVED 3. INSTALL PLATE ON RECEPTACLE FOR MICROWAVE |
|
| 01/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BLANK OPENINGS IN DEAD FRONT AT PANEL 2. CANNOT USE WHITE WIRE AS PHASE CONDUCTOR FOR DRYER CIRCUIT 3. WHERE IS NEUTRAL CONDUCTOR FOR DRYER CIRCUIT 4. NEED #10 GROUND FOR 30 AMP CIRCUIT, #12 FOR 20 AMP, #14 FOR 15 AMP 5. NEED 4 WIRE RECEPT & CORD FOR DRYER 6. BLANK SPARE SWITCH POSITION IN BATH #2 7. GROUND ALL METAL BOXES 8. HAVE 14 GAUGE WIRE ON 20 AMP CIRCUIT 9. INSTALL CONNECTORS ON ROMEX INTO 4 11/16 BOX 10. IDENTIFY NEUTRAL FOR SUB-PANEL 11. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 AND LARGER 12. USE PROPER FITTING FOR CONNECTION AT LB TO JUNCTION BOX 13. PROVIDE DETAILED & ACCURATE PANEL DIRECTORY 14. OUTDOOR RECEPTACLES TO BE GFI PROTECTED 15. PROVIDE CIRCUITS AS PER PLAN 16. CHECK FOR GFI RECEPTACLE ON ROOF |