Permit: T07CM02656

Parcel: 134113780


Addresses:

8185 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/11/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECALL WHEN READY
01/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. RECALL WHEN ALL HOOD WIRING IS COMPLETE
2. RECEPTACLE BACK OF RANGE TO BE TIED INTO ANSUL SYSTEM OR REMOVED
3. INSTALL PLATE ON RECEPTACLE FOR MICROWAVE
01/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BLANK OPENINGS IN DEAD FRONT AT PANEL
2. CANNOT USE WHITE WIRE AS PHASE CONDUCTOR FOR DRYER CIRCUIT
3. WHERE IS NEUTRAL CONDUCTOR FOR DRYER CIRCUIT
4. NEED #10 GROUND FOR 30 AMP CIRCUIT, #12 FOR 20 AMP, #14 FOR 15 AMP
5. NEED 4 WIRE RECEPT & CORD FOR DRYER
6. BLANK SPARE SWITCH POSITION IN BATH #2
7. GROUND ALL METAL BOXES
8. HAVE 14 GAUGE WIRE ON 20 AMP CIRCUIT
9. INSTALL CONNECTORS ON ROMEX INTO 4 11/16 BOX
10. IDENTIFY NEUTRAL FOR SUB-PANEL
11. INSTALL PROTECTIVE BUSHING ON CONDUCTORS #4 AND LARGER
12. USE PROPER FITTING FOR CONNECTION AT LB TO JUNCTION BOX
13. PROVIDE DETAILED & ACCURATE PANEL DIRECTORY
14. OUTDOOR RECEPTACLES TO BE GFI PROTECTED
15. PROVIDE CIRCUITS AS PER PLAN
16. CHECK FOR GFI RECEPTACLE ON ROOF