Permit: T07CM02656

Parcel: 134113780


Addresses:

8185 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALL BETWEEN CLASSROOM #1 & #2
12/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & CEILINGS IN BATH #2
12/17/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
12/13/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE WIRES WITHIN 12" OF BOXES AND EVERY 54" AFTER
2. CANNOT TIE WRAP ROMEX CABLES TO OTHER CABLES FOR SUPPORT
3. WHY ARE 14 GAUGE WIRE CONNECTED IN WITH 12 GAUGE WIRE? ARE THESE 20 AMP CIRCUITS
4. VERIFY BOXES ARE NOT OVERFILLED
5. PLANS DO NOT REFLECT ANY ELECTRIC WORK BEING DONE IN BATH #2
10/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS RMS 101, 103
2. OK HARD LIDS RM 101
10/09/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999

NEW DRYER CIRCUIT TO BE 4-WIRE BACK TO PANEL