Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL BETWEEN CLASSROOM #1 & #2 |
|
| 12/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & CEILINGS IN BATH #2 |
|
| 12/17/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION |
|
| 12/13/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE WIRES WITHIN 12" OF BOXES AND EVERY 54" AFTER 2. CANNOT TIE WRAP ROMEX CABLES TO OTHER CABLES FOR SUPPORT 3. WHY ARE 14 GAUGE WIRE CONNECTED IN WITH 12 GAUGE WIRE? ARE THESE 20 AMP CIRCUITS 4. VERIFY BOXES ARE NOT OVERFILLED 5. PLANS DO NOT REFLECT ANY ELECTRIC WORK BEING DONE IN BATH #2 |
|
| 10/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS RMS 101, 103 2. OK HARD LIDS RM 101 |
|
| 10/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 NEW DRYER CIRCUIT TO BE 4-WIRE BACK TO PANEL |