Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T07CM02654
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/05/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/04/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLOOR OK TO ROCK MECH. ONLY |
|
| 03/03/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WORK NOT DONE DATED 2/24/09 IF WORK IS NOT COMPLETE PRIOR TO NEXT INSPECTION A REFEE WILL BE APPLIED |
|
| 02/26/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DRYER VENTS OK |
|
| 02/24/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPAIR ALL DAMAGED EXHAUST TERMINALS ON OUTSIDE OF BLDG. 2. REPAIR BROKEN DRYER VENTS 3. INSULATE RETURN PLENUMS 4. SEAL KNOCKOUT HOLES IN RETURN PLENUMS AND ISOLATE LINE SET FROM EDGE OF HOLE 5. CONDENSATE DRAINS DO NOT HAVE ADEQUATE SLOPE 6. USE ONLY UL181 LISTED TAPE AND MASTICS. |
|
| 04/07/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SECOND FLOOR OK |
|
| 03/19/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE NAIL PLATES ON ALL REF. LINES PROVIDE CONDENSATE PIPING ON ALL UNITS |