Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2008 | OUTDOOR LIGHTING FINAL | Approved | ||
| 11/12/2008 | OUTDOOR LIGHTING FINAL | Partial Approval | IVRS - Inspection :* 1) TWO INSTALLED WIRES ARE HOT WIRES 2) THIRD WIRE IS A COMMON OR NEUTRAL OR A WHITE WIRE GOES TO ISOLATED BUSS BAR 3) ALL GRDS. TO GRD. BUSS, IF YOU RAN METAL CONDUIT FROM SERVICE TO SUB-PANEL, I WOULD ACCEPT THAT AS YOUR GRD. IF YOU RAN NON-METALLIC IN THE GROUND, THEN A GROUND ROD IS REQUIRED 4) REMOVE BOND WIRE FROM NEUTRAL BUSS |