Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 09/12/2008 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NEED TO CLIP (H2.5) ON GABLE END BRACING 2) NEED TO TRIM PLYWOOD ON RIDGE AT ENTRY 3) NEED TO CHECK ROOF NAILING 6" ON CENTER |
|
| 09/11/2008 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED NOT READY |
|
| 09/10/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING BRACING ON GABLE ENDS PER DETAIL 2/A5 2) NEED CLIP HEADERS-CONNECTING TO KING STUDS 3) NEED TO RE-NAIL ALL EDGES 6" ON CENTER (SHEATHING) 4) MISSING H.25 CORRECT FROM STUD TO DBL TOP PLATE 5) EXT. BEAMS AND POST NOT BUILT PER PLAN 6) MISSING H2.5 CONNECTION AT COVERED PATIO FRONT 7) WHAT SIZE BEAM NEEDED AT FRONT PATIO |