Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) LAUNDRY ROOM: WHAT IS DISCONNECT FOR ? 2) MISSING COVER PLATE 3) 1 POLE DISCONNECT-GROUND, KO'S AND SECURE |
|
| 03/05/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED ILLUMINATION OF PANELS 110.26 2. MAINTAIN DEDICATED SPACE ABOVE PANELS 3. NEW FEEDERS TO BE AS PER 408.3 |
|
| 01/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ROOMS OK PLAN REVISIONS 1. FINISH LAUNDRY |
|
| 11/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* #170, 169, 168, 167 1. PROTECT RANGE PLUG FROM DAMAGE 2. RANGE BOX MORE THAN 1/4" FROM TO SURFACE 3. INSTALL ANTI-TIP DEVICE 4. MICROWAVE RECEPTACLE TO BE ACCESSIBLE 5. FIXTURE TO SEAT TO BOX & WALL 6. RECEPTACLE BEHIND RANGE FOR COUNTER 7. BATH LIGHT 8. INSTALL ALL RANGES 9. DAMAGED NM CABLE AT ACCESS HOLE - PROTECT CABLES AT HOLE |