Permit: T07CM02634

Parcel: 126134840


Addresses:

1134 S SWAN RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/09/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
15 PSI TEST IS OK
CORRECTIONS HAVE BEEN MADE
OK FOR FINAL
11/07/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE CONDENSATE DRAINS FOR WATER HEATER VENTS
INSTALL VENT ADAPTORS PER INSTALL INSTRUCTIONS
NEED TO SEE GAS PRESSURE TEST
EXTEND WATER HEATER VENTS
PROVIDE COVERS OVER CANVAS CONNECTORS
SEAL DRYER VENT ELBOWS
11/01/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
- REMOVE ALL FOIL TAPE FROM DRYER VENTS & SEAL WITH HARDCAST FOIL GRIP #1402 UL LISTED 220 DEG. F AS PER PLANS.
- ALL CRIMPED ENDS MUST GO SAME DIRECTION AS AIR FLOW
- PROVIDE REZNO HEATER AS PER PLANS