Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL CIRCUITS AT PANELS/INSTALL PANEL DIRECTORY NEC 408.4 2. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH - NEC 200.6 3. PROVIDE PROTECTIVE BUSHING ON CONDUCTORS #4 & LARGER NEC 300.4 & 352.46 4. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH - NEC 250.119 5. SEAL OPEN KNOCKOUTS AT PANELS -- NEC 110.12 6. SEAL OPEN ENDS OF SPARE RACEWAYS - NEC 110.12 7. INSTALL MISSING RECEPT PLATE. RECEPT TO BE TIGHT TO WALL 8. INSTALL APPROVED HANDLE TIES ON CIRCUITS THAT FEED RECEPTS ON ONE YOKE 9. CONNECT GROUNDS TO WIREWAY ENCLOSURE 10. INSTALL EM LIGHTING PER PLAN 11. MISSING HEATER & SWAMP COOLER |