Permit: T07CM02634

Parcel: 126134840


Addresses:

1134 S SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL CIRCUITS AT PANELS/INSTALL PANEL DIRECTORY
NEC 408.4
2. NEUTRAL CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH - NEC 200.6
3. PROVIDE PROTECTIVE BUSHING ON CONDUCTORS #4 & LARGER NEC 300.4 & 352.46
4. GROUNDING CONDUCTORS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH - NEC 250.119
5. SEAL OPEN KNOCKOUTS AT PANELS -- NEC 110.12
6. SEAL OPEN ENDS OF SPARE RACEWAYS - NEC 110.12
7. INSTALL MISSING RECEPT PLATE. RECEPT TO BE TIGHT TO WALL
8. INSTALL APPROVED HANDLE TIES ON CIRCUITS THAT FEED RECEPTS ON ONE YOKE
9. CONNECT GROUNDS TO WIREWAY ENCLOSURE
10. INSTALL EM LIGHTING PER PLAN
11. MISSING HEATER & SWAMP COOLER