Permit: T07CM02574

Parcel: 141350730

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02574

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2007 FRAMING Approved IVRS - Inspection :*
10/03/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FILL ALL NAIL HOLE IN FHA PLATES OVER A COIL LINE NORTH WALL MAIN FLOOR
2) MINIMUM 3/4" OSB AT FIRESTOP OF DUCT CHASE AT CEILING 2ND FLOOR
3) NO METER
10/01/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PREVIOUS INSPECTION NOT COMPLETED
09/28/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT WATER HEATER PLATFORM
2) TIGHTEN ANCHOR BOLT WES OF ELECTRICAL PANEL IN GARAGE
3) NAIL DOWN FLOOR TRUSS SHEAR MAX 6" ON CENTER ABOVE REFRIDGERATOR
4) DRAFTSTOP AROUND 3" ABS IN FOYER
5) STAPLE MESH AT PEAK OF GARAGE GABLE
6) 12" MIN CLEARANCE ABOVE RECESSED LIGHT TO PEX IN FOYER 2 SPOTS
7) NAIL PLATE HOT WATER LINE IN LAUNDRY ROOM
8) SOLAR LINES FOR WATER HEATER INSTALLED AND TESTED
9) SUPPORT ABS 3" IN GARAGE CEILING
10) STOPPED INSPECTION-NOT READY