Permit: T07CM02561

Parcel: 141350720

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM02561

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2007 FRAMING Approved IVRS - Inspection :*
10/04/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIX TRUSS PER PREVIOUS INSPECTION
2) NUT NEEDED ON RISER CLAMP
10/03/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RAFTER FIX NEEDED PER PREVIOUS INSPECTION
10/02/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MINIMUM 3/4" OSB FOR FIRESTOP AT DUCT IN RAFTERS FOR FIRESTOP
2) DRAFTSTOP FLOOR OF DUCT CHASE
3) TRUSS FIX FOR RAFTERS AT GIRDER
10/01/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRUSS FIX FOR RAFTER
2) FIRESTOP MAIN DUCT CHASE AT FLOOR AND CEILING
3) HTC4 NEEDED 2 X 6 INTERIOR KITCHEN WALL
4) PROPER NAILING ON FHA STRAP UPSTAIRS
09/28/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FOUNDATION ANCHORS NORTH WALL GARAGE MAX 32" ON CENTER
2) CRIPPLES NEEDED UNDER WATER HEATER STAND FOR PROPER SUPPORT
3) 2-2 X 4 POST FROM ABOVE IN FLOOR TRUSSES ABOVE KITCHEN SINK
4) HTC4 CLIP NEEDED WEST LAUNDRY WALL TOP PLATE
5) SEAL PAPER AROUND BOXES SOUTH WALL GARAGE
6) NAIL PROTECTION TOP PLATE SOUTH WALL GARAGE
7) FILL ALL NAIL HOLES IN FHA STRAPS
8) AIR TEST ON SOLAR FOR WATER HEATER
9) NAIL PROTECT 1 1/2" ABS TOP PLATE ABOVE WATER HEATER
10) NO PITCH ON 3" ABS ABOVE KITCHEN
11) STOPPED INSPECTION-NOT READY