Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02558
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2007 | FRAMING | Approved | IVRS - Inspection :* | |
09/17/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL DOWN SHEAR PANELS IN FLOOR TRUSSES FROM ABOVE PER 303 & 508 DETAIL 2) 8-16D NAILS NEED EACH SIDE OF NOTCH IN 2 X 4 EXTERIOR WALL NORTH WALL 2ND FLOOR 3) 2-2 X6 HEADER NEEDED IN MASTER CLOSET 4) FIRESTOP MAIN TRUNK LINE 2ND FLOOR TO ATTIC 5) BLOCK OR SUPPORT 4 GANG BOX 2ND FLOOR HALLWAY 6) SECURE TEMPORARY OUTLETS 7) AIR TEST ON WATER HEATER (SOLAR) 8) TEST SHOWER PAN 9) METER BOX REQUIRED AT STREET 10) RESTRICTED DUCT HALLWAY ABOVE STAIRS 11) BLOCK AIR DUCTS 2ND FLOOR |