Permit: T07CM02550

Parcel: 10512024D


Addresses:

4040 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM02550

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/11/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE EXHAUST FAN IN E.D.C. ROOM
2) RTU-11 DID NOT SHUT DOWN ON DUCT SMOKE DETECTOR TEST
09/10/2009 MECHANICAL - FINAL Partial Approval PROVIDE AIR BALANCE REPORT
PROVIDE DUCT SMOKE DETECTOR TEST
WALK ROOF
09/10/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) AIR TEST AND BALANCE REPORT OK
2) TYPE I EXHAUST FANS TO HAVE HINGE KITS AND GASKETS
3) PROVIDE BIRD SCREEN ON DISHWASHER EXHAUST
4) RTU-11 NOT RUNNING, UNABLE TO TEST DUCT SMOKE DETECTOR, ALL OTHER D.S.D. OK
09/09/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
08/28/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) DUCT SMOKE DETECTORS TEST REPOR SHOWS 6 UNITS, THAT DID NOT PASS TEST
2) HEAT ACTIVATED INTERLOCKS ON BOTH HOODS NOT WORKING
3) SINGLE WALL FLUE PIPING CANNOT PENETRATE CEILING
4) SMOKE CONTAINMENT TEST ON HOODS NOT COMPLETE
08/25/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
08/20/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AIR BALANCE REPORT
2) DUCT SMOKE DETECTOR TEST
3) INSTALL GREASE DUCT ACCESS DOORS
4)PROVIDE SMOKE DETECTOR TEST
5)PROVIDE INSTALLATION INSTRUCTIONS FOR VENTING ON AOBART EQUOP
6)NO VENTS WITHIN 10" OF INTAKES
03/16/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*