Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM02550
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
09/11/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE EXHAUST FAN IN E.D.C. ROOM 2) RTU-11 DID NOT SHUT DOWN ON DUCT SMOKE DETECTOR TEST |
|
09/10/2009 | MECHANICAL - FINAL | Partial Approval | PROVIDE AIR BALANCE REPORT PROVIDE DUCT SMOKE DETECTOR TEST WALK ROOF |
|
09/10/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) AIR TEST AND BALANCE REPORT OK 2) TYPE I EXHAUST FANS TO HAVE HINGE KITS AND GASKETS 3) PROVIDE BIRD SCREEN ON DISHWASHER EXHAUST 4) RTU-11 NOT RUNNING, UNABLE TO TEST DUCT SMOKE DETECTOR, ALL OTHER D.S.D. OK |
|
09/09/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
08/28/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS TEST REPOR SHOWS 6 UNITS, THAT DID NOT PASS TEST 2) HEAT ACTIVATED INTERLOCKS ON BOTH HOODS NOT WORKING 3) SINGLE WALL FLUE PIPING CANNOT PENETRATE CEILING 4) SMOKE CONTAINMENT TEST ON HOODS NOT COMPLETE |
|
08/25/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/20/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE AIR BALANCE REPORT 2) DUCT SMOKE DETECTOR TEST 3) INSTALL GREASE DUCT ACCESS DOORS 4)PROVIDE SMOKE DETECTOR TEST 5)PROVIDE INSTALLATION INSTRUCTIONS FOR VENTING ON AOBART EQUOP 6)NO VENTS WITHIN 10" OF INTAKES |
|
03/16/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |