Permit: T07CM02550

Parcel: 10512024D


Addresses:

4040 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM02550

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
08/13/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) STILL WAITING FOR GREASE DUCT ACCESS DOORS
2) PROVIDE INSTALLATION INSTRUCTIONS ON HOBALT OVENS
3) PROVIDE EXTENSION COLLARS ON GRILLS WITH FLEX DUCT
08/10/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT FLEX DUCTS IN OFFICE ARE ROOM 109. OK CEILING TILES THIS AREA. WILL CHECK ON NEXT VISIT
2) K3 2ND LAYER FIRE WRAP OK
3) OK CEILING TILES FOOD STORAGE ARE
4) DUCT THRU WALL OK
08/07/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
08/03/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) K1-SECOND LAYER WRAP OK, K3-OK FOR SECOND LAYER, PROVIDE ACCESS DOORS PRIOR TO TILES BEING INSTALLED IN CEILING
2) CUSTOMER SERVICE AREA OK FOR TILES
07/31/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK 2ND LAYER K.E.-3
2) OPTICAL 200 OK TILES
07/30/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PARTIAL
FOOD COURT ( K.E. -3 ) OK FOR 1ST LAYER OF FIRE WRAP ON HORIZ. DUCT
07/29/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
07/28/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DELI HOO OK FOR 2ND WRAP ON TYPE 1 DUCT
07/27/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) K.E.-1 SMOKE TEST OK EXCEPT 3' ADAPTER FROM HOOD
2) K.E.-3 SMOKE TEST OK ON DROP FROM CURB TO 1ST ELBOW, OK TO 1ST LAYER WRAP THESE AREAS
3) DELI AREA OK FOR TILES EXCEPT AREA OF DUCT THRU WALL
07/23/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE NON COMBUSTIBLE WALL COVERING WITHIN 18" IN ALL DIRECTIONS OF HOOD OPENINGS
2) REMOVE FRP FIRST
07/22/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BAKERY/DELI HOOD EXHAUST DUCT, 1ST 4' SMOKE TEST OK, OK TO WRAP AND INSTALL
2) FOOD CART OK FOR TILES
3) PROVIDE METAL OVER SHEETROCKL PER I.M.C
07/15/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR TILES ALL SALES FLOOR
07/10/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO SHEETROCK SOUTH ENTRY HARD LID
2) CORRECTIONS DATED 7/1/09-OK
3) SEALED JOINTS OK ON ALL ROUGH DUCT
07/09/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) COLUMN LINES 6 THRU 9 OK TO TILE
2) OK TO ROCK STORE FRONT UP TO LINEAR BOXES
3) PROVIDE MAP R-4.2 AT LINEAR BOXES
07/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR SHEETROCK STARBUCKS AREA
07/01/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO SHEETROCK NORTH ENTRY VESTIBULE
2) SUPPORT FLEX OFF OF PIPES AT GRID LINE 9J,C BETWEEN 9 + 10, + E BETWEEN 10 + 11
3) OK FOR CEILING TILES FROM GRID LINE 9-12
06/26/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CHECKED SEALED JOINTS ON SUSPENDED ROUGH
2 DUCT OK TO INSULATE
06/02/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/16/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*