Permit: T07CM02550

Parcel: 10512024D


Addresses:

4040 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T07CM02550

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/06/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) LOW PRESSURE AIR TEST TODAY BETWEEN MH #4 & MH #5, ALSO BETWEEN INTERCEPTOR AND MH #5 (MANHOLE #5 AND CLEANOUT ?)
06/16/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/15/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PVC ROOF DRAIN AND OVERFLOW DRAIN AT NORTHWEST CORNER OF BLDG. OK
2. EACH VENT SHALL RISE VERTICALLY TO A POINT NOT LESS THAN SIX INCHES ABOVE THE FIXTURE BEING SERVED BEFORE OFFSETTING HORIZONTALLY
3. VENTS SHALL BE INSTALLED LEVEL OR SO DESIGNED AS TO DRAIN BACK TO THE FIXTURE BEING SERVED
4. STAND-PIPE RECEPTOR TO BE A MINIMUM OF EIGHTEEN INCHES IN LENGTH.
06/11/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ABS AND WATER PIPING AT NORTHWEST CORNER --
OK TO COVER
06/05/2009 PLUMBING - INTERMEDIATE Partial Approval OK TO COVER WALLS AT PHARMACY AND EMPLOYEE'S RESTROOM INCLUDING MOP SINK
06/04/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FOR CONCRETE AT BAKERY/DELI
06/03/2009 PLUMBING - INTERMEDIATE Partial Approval NORTHWEST PLUMBING WALL IN GROCERY -- OK TO COVER
06/02/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT HORIZONTAL PIPING IN THE WALL
PIPING MAY BE SUPPORTED TO THE METAL STUD, BUT NOT BY THE METAL STUD - ISOLATE ABS FROM METAL STUD
2. REMOVE RECTOR SEAL AT CLEANOUT
3. ADD HANGERS AS REQUIRED
02/06/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
GREASE WASTE AT PRODUCE AREA
SANITARY SEWER AT PRODUCE TO OUTSIDE BLDG. OK
WATER TEST ONE RISER TO TEN FEET