Permit: T07CM02550

Parcel: 10512024D


Addresses:

4040 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02550

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/20/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FOR TCO ELECTRICAL
NEED TO CLEAN UP LOOSE ENDS, SOME MISSING LRG
FIXTURES, COUNTERS, PANEL MAKEUP & SCAGDULES?
OK GENERATOR TEST
03/17/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
A TEST OF USED CONDUCTORS IS NEEDED TO VERIFY WIRE INTEGRITY - OK TO ENERGIZE AFTER APPROVED TEST

CHARGE ADOLPHSON AND PETERSON ACCT. $150.00
J.E. SAMU
03/17/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
REVIEWED MEGGAR RESULTS - PLEASE PROVIDE A COPY ON COMPANY LETTERHEAD FOR FILES.

MAINTAIN TORQUE FOR LUGS & CONDUCTOR TERMINATIONS