Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02550

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED GENERATOR TEST DATA
2) GFI RECEPTS REQUIRED IN FOOD PREP/KITCHENS PER 210.8 (B)
3) EM GENERATOR SIGNAGE PER 700 NEC
08/13/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED LARGER P-RINGS OR EXTENDERS FOR RECEPTS AT PEG BOARD DISPLAYS AND GONDULAS, ELECTRONICS AREA
2) FLEX OR MC OR RELOCATE CABLE NOT TO LAY ON GRID (ELECTRONIC AREA)
08/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EAST ENTRANCE CAN LIGHTS-OK
2) MAIN FLOOR WEST CEILING LIGHTS-OK
3) ENTRY VESTIBULES (NORTH AND SOUTH)-OK
07/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TRANSFORMERS T-1 & T-2 AND PANELS LD1,LD2,LP1,LP2 & LP5
06/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK HARD LIDS AT STORE MAIN ENTRANCES INSIDE AND OUT AND OFFICE SOFFITS
06/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ABOVE CEILINGS AT GRID 10-12 AND B-H
06/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONTRACTOR TO LOCK OUT/TAG OUT ELECTRICAL EQUIPMENT ONLY AUTHORIZED PERSONAL TO HAVE ACCESS TO ELECTRIC EQUIPMENT
06/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK RTU's EXCEPT 2, 3, 4, 5
06/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS. 109, 156, 159, 160, 161, 156
06/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOMS OK TO WALLS TO DATE: 131, 132, 134, 140, 143, 144, 153, 126, 133, 141, 142, 139, 134, 147, 105, 105A, 127, 128, 120, 187, 183, 173, 174, 176, 124, 120, 123, 121, 200, 201, 202, 257, 158, 115, 116, 106, 114, 110, 113, 151 - ALL ROOMS NORTH TO SOUTH ENTRY OFFICES.
06/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK DELI, BAKERY WALL ROUGH
2. VERIFY WIRING METHOD FOR SUPPLY SIDE WIRING AS REQUIRED BY MANUF. FOR RTU UNITS ON ROOF
06/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK ROUGH WALLS FOR DRESSING ROOMS, NORTH SALES FLOOR, #23 FOOD SERVICE
2. RECEIVED LETTER OF TORQUE FROM CASCADE ELEC. NEED ONE FROM SITE UTILITIES FOR SECONDARY TERM.
3. OK LOAD FEEDERS TO DIST. PANELS
4. POST BOND FOR TEMP POWER FOR TEST
5. NEED TO BOND WATER, GAS, PVC, EDC, CFI MAIN TEST
6. SECONDARYS NOT IN SES YET
06/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK EXTERIOR WALL ROUGH LOADING DOCK AREA
ROOMS #131, 132, 134, 142, 140, 143, 144, 153, 126
06/04/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROCK AREA NOT READY
FINISH N.WALL AND LIGHTS/FANS EAST WALL
06/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOUTH PERIMETER WALL ROUGH
05/26/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/13/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TEP PRIMARY, INSTALL WIRING RIBBON
04/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/03/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/25/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK 2" PVC BUILDING OUT FOR SITE LIGHTING
2. OK 2 - 3/4" PVC JEWELRY
3. OK #4 TO 2 - GROUND RODS TEMP POWER
03/19/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEIVED MEGGER REPORT
OK LAST 30' PVC 8-10 AND A-B 2 - 2"
OK UNDER SLAB AS MARKED ON CASCADES PLAN
02/05/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
DISCUSSED PRE-CAST WALLS WITH ELECTRICIAN
OK TO POUR ALL PRE-CAST WALLS