Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02550
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEIVED GENERATOR TEST DATA 2) GFI RECEPTS REQUIRED IN FOOD PREP/KITCHENS PER 210.8 (B) 3) EM GENERATOR SIGNAGE PER 700 NEC |
|
08/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED LARGER P-RINGS OR EXTENDERS FOR RECEPTS AT PEG BOARD DISPLAYS AND GONDULAS, ELECTRONICS AREA 2) FLEX OR MC OR RELOCATE CABLE NOT TO LAY ON GRID (ELECTRONIC AREA) |
|
08/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) EAST ENTRANCE CAN LIGHTS-OK 2) MAIN FLOOR WEST CEILING LIGHTS-OK 3) ENTRY VESTIBULES (NORTH AND SOUTH)-OK |
|
07/02/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TRANSFORMERS T-1 & T-2 AND PANELS LD1,LD2,LP1,LP2 & LP5 |
|
06/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK HARD LIDS AT STORE MAIN ENTRANCES INSIDE AND OUT AND OFFICE SOFFITS |
|
06/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILINGS AT GRID 10-12 AND B-H |
|
06/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CONTRACTOR TO LOCK OUT/TAG OUT ELECTRICAL EQUIPMENT ONLY AUTHORIZED PERSONAL TO HAVE ACCESS TO ELECTRIC EQUIPMENT |
|
06/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK RTU's EXCEPT 2, 3, 4, 5 |
|
06/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS. 109, 156, 159, 160, 161, 156 |
|
06/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROOMS OK TO WALLS TO DATE: 131, 132, 134, 140, 143, 144, 153, 126, 133, 141, 142, 139, 134, 147, 105, 105A, 127, 128, 120, 187, 183, 173, 174, 176, 124, 120, 123, 121, 200, 201, 202, 257, 158, 115, 116, 106, 114, 110, 113, 151 - ALL ROOMS NORTH TO SOUTH ENTRY OFFICES. |
|
06/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK DELI, BAKERY WALL ROUGH 2. VERIFY WIRING METHOD FOR SUPPLY SIDE WIRING AS REQUIRED BY MANUF. FOR RTU UNITS ON ROOF |
|
06/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK ROUGH WALLS FOR DRESSING ROOMS, NORTH SALES FLOOR, #23 FOOD SERVICE 2. RECEIVED LETTER OF TORQUE FROM CASCADE ELEC. NEED ONE FROM SITE UTILITIES FOR SECONDARY TERM. 3. OK LOAD FEEDERS TO DIST. PANELS 4. POST BOND FOR TEMP POWER FOR TEST 5. NEED TO BOND WATER, GAS, PVC, EDC, CFI MAIN TEST 6. SECONDARYS NOT IN SES YET |
|
06/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK EXTERIOR WALL ROUGH LOADING DOCK AREA ROOMS #131, 132, 134, 142, 140, 143, 144, 153, 126 |
|
06/04/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROCK AREA NOT READY FINISH N.WALL AND LIGHTS/FANS EAST WALL |
|
06/02/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOUTH PERIMETER WALL ROUGH |
|
05/26/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/13/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TEP PRIMARY, INSTALL WIRING RIBBON |
|
04/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/25/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 2" PVC BUILDING OUT FOR SITE LIGHTING 2. OK 2 - 3/4" PVC JEWELRY 3. OK #4 TO 2 - GROUND RODS TEMP POWER |
|
03/19/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED MEGGER REPORT OK LAST 30' PVC 8-10 AND A-B 2 - 2" OK UNDER SLAB AS MARKED ON CASCADES PLAN |
|
02/05/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DISCUSSED PRE-CAST WALLS WITH ELECTRICIAN OK TO POUR ALL PRE-CAST WALLS |