Permit: T07CM02550

Parcel: 10512024D


Addresses:

4040 N ORACLE RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T07CM02550

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/16/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G FOR LTG. COMPLETE
05/28/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK EM GEN. CONDUITS
2. OK PHARMACY ROUGH WALLS
05/26/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
05/13/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
05/12/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
05/11/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
05/08/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
9 - 1" PVC FROM SERVICE CENTER ON NORTHEAST CORNER TO WEST CORNER TO BAKERY DELI ALL START BREACHING OFF OK - TRANSFORMER PAD TO LOADING DOCK 20' BEYOND OK TRENCH PRIMARY - SECONDARY 8 - 4" PVC TO SWITCH GEAR FROM TRANS OK
04/28/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
04/23/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/13/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/09/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
POLE BASES NORTH AND EAST SEE PLANS
04/07/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/03/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/01/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
03/31/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK REMAINDER OF COMM. CONDUITS U.G.
03/30/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 4 POLE BASES AS MARKED
03/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/26/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 - 4" PHONE CONDUIT
PEDESTAL TO PEDESTAL
03/25/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/24/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
03/24/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK LAST 60'
2 - 3' AND 1 - 2" PVC
6-8 AND K-L

OK 2" PVC FOR TEMP POWER FEEDER
OK POLE TO POLE AS MARKED
03/23/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
03/23/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE TO POLE AS MARKED
03/20/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 3/0 OUT UNDER SLAB FOR BUILDING STEEL
OK POLE TO POLE AS MARKED
03/19/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS 10-13 AND B-D ELECTRONICS
03/18/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/16/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
TEMP LIGHTING:
1. LABEL DISCONNECT
2. FILL UNUSED OPENING
3. USE APPROVED TERMINAL END WITH STRANDED CONDUCTOR
4. WAITING ON APPROVAL FOR OUTDOOR LIGHTING CODES

OK 20' OF GROUND ROD
OK 2 POLE CONDUIT PHARMACY
03/13/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
03/13/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK CONTINUATION TO PVC FROM COLUMNS 8-10 AND D-G
OK POLE BASE AS MARKED
OK CONTINUATION TO PVC FROM COLUMN 10-8 AND J-K
03/12/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC POLE TO POLE AS MARKED
OK 130' CONTINUATION 2" PVC WEST UNDER SLAB
03/11/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
03/06/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE TO POLE AND POLE BASES AS MARKED
03/05/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS COLUMNS 6-8 AND A-D
OK PVC CONDUITS ELECTRONICS
03/03/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
02/26/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G BUILDING SLAB GRID LINES 1 TO 8 AND A TO C
02/25/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
02/19/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 POLE BASES AS MARKED
02/18/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
02/12/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK AS MARKED ON PLANS
02/05/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
02/04/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
02/03/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK AS MARKED
02/02/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 5 - 4" PVC CONDUIT OUT OF XFMR #7 - 10'
01/30/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC FOR LIGHTING AS MARKED
01/29/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 6 POLE BASES AS MARKED
01/28/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1" PVC AS MARKED ON PLANS
01/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G 1" PVC FOR PARKING LOT LIGHTING
AS INDICATED ON SL2.0