Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02547
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOND RACEWAY BETWEEN GUTTER & DISCONNECT 2. INSTALL PROTECTIVE BUSHING 3. MARK "SERVICE DISCONNECT" 4. REVISE PLANS FOR SERVICE SHOWING WHAT IS ON SITE |
|
03/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE OPEN WIRES IN CEILING ABOVE REGISTERS 2. PROVIDE DISCONNECT FOR MENU BOARD - NEC 600.6 3. SERVICE AS IS DOES NOT MATCH PLAN - NEED REVISION 4. MARK "SERVICE DISCONNECTS" NEC 230.70 5. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT NEC 250.24, 250.28 6. HAVE ELECTRICAL CONTRACTOR ON SITE TO OPEN SERVICE EQUIPMENT 7. BOND SERVICE RACEWAYS - NEC 250.92 8. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTION -- NEC 250.8 9. INSTALL IG GROUND TO PANEL FROM SERVICE & INSTALL IG GROUND BAR |
|
03/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SUPPORT M/C CABLES TO CANS AS PER CODES 2. DEVICES MORE THAN 1/4" & 1/8" AROUND - 314.20, 314.21 3. IDENTIFY ISOLATED GROUND CONDUCTOR 4. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATION, LEGIBLE AND DISTINGUISHABLE FROM ONE ANOTHER 5. LABEL DISCONNECT - MAIN 6. USE APPROVED HARDWARE OTHER THAN DRYWALL SCREWS |