Permit: T07CM02547

Parcel: 13613001W

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02547

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/21/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND RACEWAY BETWEEN GUTTER & DISCONNECT
2. INSTALL PROTECTIVE BUSHING
3. MARK "SERVICE DISCONNECT"
4. REVISE PLANS FOR SERVICE SHOWING WHAT IS ON SITE
03/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE OPEN WIRES IN CEILING ABOVE REGISTERS
2. PROVIDE DISCONNECT FOR MENU BOARD - NEC 600.6
3. SERVICE AS IS DOES NOT MATCH PLAN - NEED REVISION
4. MARK "SERVICE DISCONNECTS" NEC 230.70
5. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT NEC 250.24, 250.28
6. HAVE ELECTRICAL CONTRACTOR ON SITE TO OPEN SERVICE EQUIPMENT
7. BOND SERVICE RACEWAYS - NEC 250.92
8. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTION -- NEC 250.8
9. INSTALL IG GROUND TO PANEL FROM SERVICE & INSTALL IG GROUND BAR
03/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT M/C CABLES TO CANS AS PER CODES
2. DEVICES MORE THAN 1/4" & 1/8" AROUND - 314.20, 314.21
3. IDENTIFY ISOLATED GROUND CONDUCTOR
4. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATION, LEGIBLE AND DISTINGUISHABLE FROM ONE ANOTHER
5. LABEL DISCONNECT - MAIN
6. USE APPROVED HARDWARE OTHER THAN DRYWALL SCREWS