Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL PREVIOUS INSPECTION ITEMS 2. NEED REVISION TO PLANS FOR ANY CHANGES 3. TIME CLOCK TO BE SECURELY MOUNTED. NOT TO BE INSTALLED IN SERVICE EQUIPMENT. 4. HAVE 100% COMPLETE BY NEXT INSPECTION TO AVOID REFEE |
|
| 04/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE PEDESTAL UNLOCKED FOR INSPECTION 2. SPLICES IN OPEN BOTTOM BOXES TO BE LISTED FOR WET LOCATION 3. CONNECT EQUIPMENT GROUNDING CONDUCTOR TO LIGHT POLE 4. EXISTING CIRCUIT WAS TO BE REMOVED. SEE PLANS. 5. IS PHOTO CLOCK INSTALLED |