Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM02538
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 08/01/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) ITEMS BELOW NOT FIXED 2) UNCOVER SOIL PIPE REPAIR FOR INTERMEDIATE INSPECTION |
|
| 07/27/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 2, 3, 4, 5, 7, 9 & 10 FROM 7/23/07 INSPECTION NOT DONE |
|
| 07/23/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING HIP HANGERS REAR PORCH 2) REAR PORCH ROOF OSB TURNED WRONG WAY BLKS AT 24" ON CENTER 3) DBL 2 X 4 REAR PORCH SIDE BEAM SPLICE, MUST BE FULL MEMBER 4) 1ST/2ND FLOOR STRAPS AT 2ND FLOOR ABOVE GARAGE GLU LAM 5) WILL NEED FLOOR REPAIR DETAIL 1ST FLOOR SHOWER TO VENT 6) 7/SD4 TIE SHEARWALL TOP TO 2ND FLOOR, SPEC PAGE SEE #D STRAPS CS20 AT 32" ON CENTER 7) BLK BELOW PLATES 2ND FRONT POP OUTS BEARING ON 1/2 OSB 8) EAST SIDE FRIEZE BOARDS NOT NAILED 9) GUSSET PLATE MISSING FRONT 2ND FLOOR ROOF GABLE 10) 6 TRUSSES IN FROM REAR ROOF SOUTH, 1ST FULL ROW OSB FROM TOP OF RIDGE JOINT NOT NAILED, MARKED ON FLOOR |