Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCK UNDER H20 HTR PLATFORM, AT FIREWALL 2) FEEDER FROM SERVICE TO SUB PANEL, NOT PER PLAN #4=65 AMPS, LOAD CALCS, 43 AMPS. SERVICE PANEL DIAGRAM CALLS FOR 125 AMP BREAKER ? |
|
| 02/13/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/12/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/04/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|