Permit: T07CM02529

Parcel: 13818017C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/26/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BLOCK UNDER H20 HTR PLATFORM, AT FIREWALL
2) FEEDER FROM SERVICE TO SUB PANEL, NOT PER PLAN #4=65 AMPS, LOAD CALCS, 43 AMPS. SERVICE PANEL DIAGRAM CALLS FOR 125 AMP BREAKER ?
02/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/12/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/04/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/29/2008 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled